本产品按国家标准GB 14094、GB 12527制造。产品适用于额定电压10kV及以下架空电力线路中。 These cable are manufactured to GB 14049 and GB 12527.They are suitable for use as power 1ines with rated Vo1tages up to 10 kV.
二、型号、名称、范围 (见表1-1) Type designation and application (Table1-1)
三、规格 Size
1.单芯single core
2.铜铝芯标称截面:16mm2-300mm2 Nominal cross-section of copper and aluminium conductors:16mm2-300mm2
3. 钢铝绞线芯标称截面:见GB 1179 Nominal cross-section of ACSR:refer to GB 1179
四、使用特性 Instructions for application
1.额定电压1kV、10kV Rated vo1tage:1kV,10kV
2.电缆敷设温度应不低于-20℃; The temperature for cable installation shall not be not 1ess than -20℃.
3.电缆导体最高长期允许工作温度 The Max. long-term operating temperatures for cable conductors. |
|
聚氯乙烯绝缘70℃ 70℃ for PVC insulation 高密度聚乙烯绝缘75℃ 75℃ for HDPE insulation 交联聚乙烯绝缘90℃ 90℃ for XLPE insulation
4.短路时(最长持续时间不超过5s)电缆的最高温度: Max temperature for cables when short-circuited (lasting for max 5 seconds): 聚氯乙烯绝缘160℃ 160℃ for PVC insulation 高密度聚乙烯绝缘150℃ 150℃ for HDPE insulation 交联聚乙烯绝缘250℃ 250℃for XLPE insulation
5.电缆的允许弯曲半径 Permissible bend radius of cables: 1kV电缆外径 (D)小于25mm者,应不小于4D; 1kV cables:For cable overall diameter (D)<25mm,not smaller than 4D; 外径为25mm及以上者应不小于6D For cable overall diameter (D)≥25mm,not smaller man 6D.
五、电缆计算外径及最小拉断力(见表2-2) Calculated cable overall diameter and breaking strength (Table 2-2).
|